Wire Size Calculator

Find the correct AWG wire size for any electrical circuit based on amperage, distance, and voltage. Calculate voltage drop percentage and wire resistance.

A
ft
%
Recommended AWG
Voltage Drop
Voltage Drop %
Wire Resistance
Extended More scenarios, charts & detailed breakdown
ft
Minimum AWG
Voltage Drop %
Breaker Size
NEC Notes
Professional Full parameters & maximum detail
A
ft
V
$

Wire Selection

Recommended AWG
Voltage Drop %

Ampacity & Derating

Derating Factor (bundled)
Adjusted Ampacity

Material & Cost

Total Wire Length (both conductors)
Estimated Wire Cost

How to Use This Calculator

  1. Enter the amperage of the circuit.
  2. Enter the one-way distance in feet from the panel to the load.
  3. Select the system voltage (120V or 240V).
  4. The calculator recommends the minimum AWG size and shows actual voltage drop.

Formula

Voltage Drop = 2 × L × I × R (for single-phase)

where L = one-way length (ft), I = current (A), R = resistance per foot (Ω/ft)

Voltage Drop % = (Voltage Drop / System Voltage) × 100

Example

Example: 20A circuit, 75 ft run, 120V, copper → Use 10 AWG (voltage drop = 2.5%)

Frequently Asked Questions

  • A 20-amp circuit requires 12 AWG copper wire at minimum per NEC code. For long runs (over 50 ft) check the voltage drop — you may need 10 AWG.
  • Voltage drop = (2 × Length × Current × Resistance per foot) for single-phase. The NEC recommends keeping voltage drop under 3% for branch circuits.
  • Lower AWG numbers mean larger wire diameter. AWG 14 is common for 15A, AWG 12 for 20A, AWG 10 for 30A, AWG 8 for 40A, and AWG 6 for 55A circuits.
  • Copper is preferred for most applications. Aluminum wire is cheaper and lighter but requires connectors rated for aluminum and is 2 AWG sizes larger for the same ampacity.
  • Voltage drop % is how much voltage is lost along the wire. The NEC recommends max 3% for branch circuits and 5% total (feeder + branch). High drop causes dimming and inefficiency.

Related Calculators